RM Series
 
 
 
 
The AAON® RM Series continues the industry leading performance of the RK Series. All models are equipped with backward-inclined plenum fans for energy efficient delivery of airflow and stable static pressure. For installation flexibility RM units are available in two cabinet sizes from 2 to 15 tons cooling capacity and mount to one common curb size. Similarly, RM units from 16 to 30 ton share a common curb. The use of two curb sizes for these models allows maximum flexibility and minimum installation time at the job site. RM Series
UnitRMNominal CapacityEERGasElectricDimensions - inches
SizeModelin tonsRatingMBh InputkWLength (HW*)WidthHeight
A022.312.83 sizes
to
180
Up to 4078.0 (118.0)75.035.4
033.012.8
044.211.4
055.111.8
066.710.4
077.910.3
B088.411.23 sizes
to
390
Up to 6078.0 (118.0)87.043.4
1010.511.0
1313.210.8
1514.410.6
C1615.412.23 sizes
to
480
Up to 100105.8 (154.1)98.959.5
1817.811.7
2019.811.5
2524.910.4
3026.09.5
Note: 2 to 5 ton models are SEER rated.* Length with AAONAIRE® energy recovery wheel.
 
Standard Features
  • Compressors, controls and heating components are located in a single isolated compartment
  • Scroll compressors are installed on a sheet metal deck and rubber isolation mounted for quiet efficient operation
  • Thermostatic expansion valves on all DX coils
  • Manual reset high pressure cutoff
  • Automatic reset low pressure cutoff
  • Roof sloped and cross-broken for proper drainage
  • Bottom access return and supply air
  • Single point power connection
  • Double wall access doors with stainless hinges
  • Slide out blower assembly for easy service
  • Notched blower drive belts
  • Direct drive condenser fans
  • G90 galvanized cabinet construction
  • Gray polyurethane paint passes 2000 hour salt spray test
  • Run test report, wiring diagram, installation manual and startup form are located in control access compartment
 
Optional Features
  • Economizer - full modulating or 3-position outside air
  • Power exhaust with or without the AAONAIRE® energy recovery heatwheel
  • Gas Heat Exchanger - stainless steel
  • Blower Motors - oversized and/or high efficiency
  • Blower Fan - VFD volume control
  • Air Filter - multiple options and monitoring devices
  • GFI convenience outlet
  • Smoke Detectors or firestats - return and/or supply air
  • Compressor isolation valves
  • Phase and brown-out protection
  • Disconnect switch
  • Burglar bars on the return and supply air openings
  • All double wall construction
  • Drain Pan - stainless steel
  • Horizontal supply and return air curb
 
 